北京市某饭店通风空调设计
Error! No bookmark name 。该楼的工程概况为:总建筑面积约13132m2,, 地上十层,地下一层。
空调设计中,一至三层的大空间(大堂、西餐厅、宴会厅等)采用全空气一次回风的空气处理方案。空气处理机组采用超薄吊顶式空气处理系统。其余空调房间(中餐厅、客房、贵宾房等)采用风机盘管加新风系统。新风由设置在走廊内的吊顶新风机组处理后送入各房间。
在冷负荷计算的基础上完成主机和风机盘管的选型,并通过风量、水量的计算确定风管路和水管路的规格,并校核最不利环路的阻力和压头用以确定新风机和水泵。
空调用制冷机房设在地下室,选用两台螺杆式冷水机组。夏天使用冷水机组提供的7/12℃的冷水。水管路采用两管制。
关键词:空调设计,全空气系统,风机盘管系统,冷水机组
Design of Ventilating and Air Conditioning
for restaurant in Beijing
Abstract The air conditioning engineering of one Hotel with ten layers in Beijing was designed. The engineering general situation of the residence's floor is:Total building area roughly 13132 m2, high m, on the ground 10 layer, underground 1 layer
In air conditioning design, 1F and 3F big spaces ( great hall, western-style restaurant, banquet hall and so on) use concentrated all-air system. The air processing unit is microtome-ceil air system. Other air conditioned rooms (example Chinese dinner service, guest room, VIP Room and so on) use CFU and all-fresh air system, the outside air processes by new atmosphere unit which establishes in ceiling, and then sends in to various rooms.
The main-machine and fan coils’choice were based on the calculation of cold-load. And through the numeration of blast volume and water flux,the standard of air duct and water pipe was determined. The most disadvantage resistance and pressure of the loop-road were checked up to ensure the machine of fresh-air and water pump.
The Air conditioning refrigeration engine room is located in the basement, Selecting two screw rods types cold water unit, it uses 7/12 ℃ cold water which the cold water unit provides in summer. The water supply uses two pipelines.
Key word: Air conditioning design, entire air system, air blower plate tube system, cold water unit.

设计说明书
1 工程概况


设计对象所在地:北京市某饭店
土建资料:本大楼是一个具备餐饮、客房等功能的建筑,总建筑面积为13132平方米,,地下室深4m。
该饭店地下室主要为设备机房,储藏间,给排水专业设备间,配电间等;地面一层为大厅及管理用房,;二层主要为办西餐厅,

毕业设计(论文)-北京市某饭店通风空调设计 来自淘豆网www.taodocs.com转载请标明出处.