下载此文档

北京市某饭店通风空调设计 毕业论文.doc


文档分类:建筑/环境 | 页数:约52页 举报非法文档有奖
1/52
下载提示
  • 1.该资料是网友上传的,本站提供全文预览,预览什么样,下载就什么样。
  • 2.下载该文档所得收入归上传者、原创者。
  • 3.下载的文档,不会出现我们的网址水印。
1/52 下载此文档
文档列表 文档介绍
1 北京市某饭店通风空调设计摘要本设计为北京某十层饭店空调工程设。该楼的工程概况为:总建筑面积约 13132m 2, 高 , 地上十层,地下一层。空调设计中, 一至三层的大空间( 大堂、西餐厅、宴会厅等) 采用全空气一次回风的空气处理方案。空气处理机组采用超薄吊顶式空气处理系统。其余空调房间( 中餐厅、客房、贵宾房等) 采用风机盘管加新风系统。新风由设置在走廊内的吊顶新风机组处理后送入各房间。在冷负荷计算的基础上完成主机和风机盘管的选型, 并通过风量、水量的计算确定风管路和水管路的规格,并校核最不利环路的阻力和压头用以确定新风机和水泵。空调用制冷机房设在地下室,选用两台螺杆式冷水机组。夏天使用冷水机组提供的 7/12 ℃的冷水。水管路采用两管制。关键词: 空调设计,全空气系统,风机盘管系统,冷水机组 2 Design of Ventilating and Air Conditioning for restaurant in Beijing A bstract The air conditioning engineering ofone Hotel with ten layers in Beijing was designed. The engineering general situation of the residence's floor is:Total building area roughly 13132 m2 , high m,on the ground 10 layer, underground 1 layer In air conditioning design, 1F and 3F big spaces ( great hall, western-style restaurant, banquet hall and soon) use concentrated all-air system. The air processing unit is microtome-ceil air system. Other air conditioned rooms (example Chinese dinner service, guest room, VIP Room and soon) use CFU and all-fresh air system, the outside air processes by new atmosphere unit which establishes in ceiling, and then sends in to various rooms. The main-machine and fan coils ’ choice were based on the calculation of cold-load. And through the numeration of blast volume and water flux , the standard of air duct and water pipe was determined. The most disadvantage resistance and pressure of the loop-road were checked up to ensure the machine of fresh-air and water pump. The Air conditioning refrigeration engine room is located in the basement, Selecting two screw rods types cold water unit, it uses 7/12 ℃ cold water which the cold water unit provides in summer. The water supply uses two pipelines. Key word: Air conditioning design, entire air system, air blower plate tube system, cold water 设计说明书 1工程概况 . 设计依据 设计原始资料设计对象所在地:北京市某饭店土建资料:本大楼是一个具备餐饮、客房等功能的建筑,总建筑面积为 13132 平方米,建筑高度为 米,地下室深 4m。该饭店地下室主要为设备机房,储藏间,给排水专业设备间,配电间等;地面一层为大厅及管理用房,层高 米;二层主要为办西餐厅,层高 米;三层为宴会厅,层高 米;四层为中餐厅及贵宾房,层

北京市某饭店通风空调设计 毕业论文 来自淘豆网www.taodocs.com转载请标明出处.

相关文档 更多>>
非法内容举报中心
文档信息
  • 页数52
  • 收藏数0 收藏
  • 顶次数0
  • 上传人酒酿小樱桃
  • 文件大小0 KB
  • 时间2016-07-15