汲取福岛事故经验教训提高核电平安水平 柴国旱 2021年9月26日,江苏扬州 * 福岛第一核电厂俯瞰图 惊心动魄的事故景象 3月11日14:46发生地震,海啸来袭;导致全厂完全断电、失去最终热阱; 3月12日15:36,ormer Units 1 & 2 startup transformer Units 3 & 4 startup transformer D/G Unit 1 emergency system power supply Unit 2 emergency system power supply Unit 3 emergency system power supply Unit 4 emergency system power supply D/G D/G 1H 1A 1B bus-bar D/G D/G D/G 2H 2A 2B bus-bar D/G D/G D/G 3H 3A 3B bus-bar D/G D/G D/G 4H 4A 4B bus-bar P Cooling system P Cooling system P Cooling system P Cooling system Some surviving off-site power sources ・Inspection of the Iwaido Line 1 was in progress from before the earthquake. ・Iwaido Line 2 did not shut down, but a failure occurred, and was thus shut down for restoration ・Tomioka Line 2 was shut down to prevent a transmission grid failure. ・ The DG× signifies loss of function due to either “M/C failure,〞 “loss of sea water system,〞 or “DG main unit failure.〞 [Power supply at Fukushima Daini: Immediately after the tsunami] 福岛第二核电厂在受海啸袭击后的供电状态 * 日本BWR在严重事故管理方面的改进 * 日本核电厂抗震性能评估及抗震改进 * 日本核电厂的隔震建筑-现场应急指挥中心 IAEA福岛事故国际专家调查团 2021年5月24日-6月1日,IAEA组织了福岛事故国际专家调查团 2021年6月20日IAEA核平安部长级会议前正式发布福岛事故调查报告 15条结论 16条经验 * 日本政府关于福岛事故报告 在2021年6月20日IAEA核平安部长级会议前提交 五类教训,共28条 第一类教训-加强严重事故预防措施 第二类教训-强化严重事故的对策 第三类教训-加强核应急响应 第四类教训-加强平安根底工作 第五类教训-全面贯彻平安文化 * 美国核管会 美国NRC于2021年7月13日发布?增强二十一世纪反响堆平安的建议?,共12条建议 梳理法规体系 确保预防措施 增强缓解能力 加强应急准备 提高工作效率 * 福岛事故的深远影响 福岛事故极大地动摇了公众对核电平安的信心。 福岛事故之后,有关核能和平利用的平安理念和平安要求都将可能调整 目前状况不明 核平安相关活动的组织机构和工作模式的可能调整 国际组织 监管机构 持照模式 透明度、公众参与 * 核电平安的剩余风险不容无视 核电厂的平安性 三里岛事故、切尔诺贝利事故 平安研究、运行经验反响 核电厂并非原来想象的那么巩固 核电厂发生严重事故的可能性不可能被完全消除 其风险主要来自外部事件的影响 剩余风险 陡变效应 与内部事故相比,针对外部事件的设计考虑需要加强 设计基准 超设计基准 * 应对超设计基准的外部事件 确认设计基准的适当性 开展更加深入的调查和分析 关注外部事件引发